Carbon Dioxide Meter with PID Output
FEATURES
• Real time measuring ambiance carbon dioxide and temperature and relative humidity
• NDIR infrared CO2 sensor with Self Calibration which makes CO2 measurement more accurate and reliable.
• Up to 15 years lifetime of CO2 sensor
• Provide one or two 0~10VDC/4~20mA which can be choosen linear outputs or PID control output
• One passive relay output is optional. It can control a fan or a CO2 generator. The control mode is easily selected.
• The 3-color LED indicates three CO2 level ranges
• Optional OLED screen displays CO2/Temp/RH measurements
• Buzzer alarm available
• RS485 interface with Modbus RTU
• 24VAC/VDC power supply
• CE-approval
TECHNICAL SPECIFICATIONS
| General Data | ||
| Power supply | 24VAC/VDC± 10% | |
| Consumption | 3.5 W max. ; 2.0 W avg. | |
| Analog outputs | One 0~10VDC/4~20mA for CO2 measurementTwo 0~10VDC/4~20mA for CO2/Temperature measurements PID control output is selectable | |
| Relay output | One passive relay output (max.5A) with the control mode selection (control a fan or a CO2 generator) | |
| RS485 interface | Modbus protocol, 4800/9600(default)/19200/38400bps; 15KV antistatic protection, independent base address. | |
| LED light selectable | 3-color mode (default) Green: ≤1000ppm Orange: 1000~1400ppm Red: >1400ppmRed flashing: CO2 sensor faulty | Working light mode Green on: workingRed flashing: CO2 sensor faulty |
| OLED Display | Display CO2 or CO2/temp. or CO2/Temp./ RH measurements | |
| Operation condition | -20~60℃; 0~99%RH, non condensing | |
| Storage condition | 0~50℃, 0~60%RH | |
| Net Weight / Dimensions | 190g /117mm(H)×95mm(W)×36mm(D) | |
| Installation | wall mounting with 65mm×65mm or 2”×4”wire box | |
| Housing and IP class | PC/ABS fireproof plastic material, protection class: IP30 | |
| Standard | CE approval | |
| Carbon Dioxide | ||
| Sensing element | Non-Dispersive Infrared Detector (NDIR) | |
| CO2 measuring range | 0~2,000ppm (default)0~5,000ppm (selected in the advanced setup) | |
| CO2 Accuracy | ±60ppm + 3% of reading or ±75ppm (whichever is greater) | |
| Temperature dependence | 0.2% FS per℃ | |
| Stability | <2% of FS over life of sensor (10 year typical) | |
| Pressure dependence | 0.13% of reading per mm Hg | |
| Calibration | ABC Logic Self Calibration Algorithm | |
| Response time | <2 minutes for 90% step change typical | |
| Signal update | Every 2 seconds | |
| Warm-up time | 2 hours (first time) / 2 minutes (operation) | |
| Temperature and RH (option) | ||
| Temperature sensor (selectable) | Digital integrated temperature and humidity sensor SHT, or NTC thermistor | |
| Measuring range | -20~60℃/-4~140F (default) 0~100%RH | |
| Accuracy | Temp.: <±0.5℃@25℃ RH: <±3.0%RH (20%~80%RH) | |