Carbon Dioxide Sensor NDIR

Short Description:

Model: F2000TSM-CO2 Series
Key words:
Cost-effective
CO2 detection
Analog output
Wall mounting

 

Short Description:
This is a low-cost CO2 transmitter designed for applications in HVAC, ventilation systems, offices, schools, and other public places. NDIR CO2 sensor inside with Self-Calibration and up to 15 years lifetime. One analog output of 0~10VDC/4~20mA and six LCD lights for six CO2 ranges within six CO2 ranges make it unique. RS485 communication interface has 15KV anti-static protection, and its Modbus RTU can connect any BAS or HVAC systems.


Brief Introduction

Product Tags

FEATURES

Real-time detecting CO2 level.
NDIR infrared CO2 module inside with four CO2 detection range selectable.
CO2 sensor has Self-Calibration Algorithm and 15 years lifetime
Wall-mounting
Providing one analog output with voltage or current selectable
0~10VDC/4~20mA selectable easily via jumpers
Special “L” series with 6 lights indicates CO2 level and makes CO2 level show clearly.
Design for HVAC, ventilation systems, offices, or other public places.
Modbus RS485 communication interface optional: 15KV antistatic protection, independent address setting
CE-Approval

TECHNICAL SPECIFICATIONS

Gas detected Carbon Dioxide (CO2)
Sensing element Non-Dispersive Infrared Detector (NDIR)
Accuracy@25℃(77℉),2000ppm ±40ppm + 3% of reading or ±75ppm (whichever is greater)
Stability <2% of FS over life of sensor (15 yr typical)
Calibration interval ABC Logic Self Calibration System
Response time <2 minutes for 90% step change
 Warm up time 2 hours (first time)/2 minutes (operation)
 CO2 measuring range 0~2,000ppm / 0~5,000ppm selectable in orders 0~20,000ppm / 0~50,000ppm just for TSM-CO2-S series
Sensor life Up to 15 years
Power supply 24VAC/24VDC
Consumption 1.5 W max. ; 0.8 W avg.
Analog outputs 0~10VAC or 4~20mA selectable by jumpers
 Relay output 1X2A switch loadFour set points selectable by jumpers

 

6 LED lights(just for TSM-CO2-L series) From left to right:Green/Green/Yellow/Yellow/Red/Red 1st green light on as CO2 measurement≤600ppm,

1st and 2nd green lights on as CO2 measurement>600ppm

and≤800ppm,

1st yellow light on as CO2 measurement>800ppm and≤1,200ppm,

1st and 2nd yellow lights on as CO2 measurement>1,200ppm and≤1,400ppm,

1st red light on as CO2 measurement>1,400ppm and≤1,600ppm,

1st and 2nd red lights on as CO2 measurement>1,600ppm.

 Modbus interface Modbus RS485 interface9600/14400/19200(default)/28800 or 38400bps (programmable selection), 15KV antistatic protection.
Operation conditions 0~50℃(32~122℉); 0~95%RH, non condensing
Storage conditions 0~50℃(32~122℉)
Net weight 180g
Dimensions 100mm×80mm×28mm
Installation standard 65mm×65mm or 2”×4”wire box
Approval CE-Approval

  • Previous:
  • Next:

  • Write your message here and send it to us